Hilscher COM-MBP
|
|
Hilscher COM-MBP
|
| Communication Module Modbus Plus
|
|
|
|
|
|
| Product
|
COM-MBP
|
|
|
|
| Description
|
Communication Module
|
| Modbus Plus
|
| Order seperately
|
Evaluation kit COM-MBP-EKIT
|
|
|
|
| Card format
|
COM
|
|
|
|
| Bus interface
|
Dual-Port-Memory
|
|
|
|
| Dual-Port-Memory
|
2 KByte
|
| Interrupt
|
Yes
|
| Connector
|
Female post connector 40-pin
|
|
|
|
| Modbus Plus interface
|
|
|
|
| Transmission rate
|
1 MBaud
|
| Controller
|
ASIC Schneider Automation
|
| Interface
|
RS485, optically isolated
|
| Connector
|
DSub-female connector 9-pin
|
|
|
|
| Diagnostic interface
|
RS232C, non-isolated
|
|
|
|
| Connector
|
Male post connector 10-pin
|
|
|
|
| Display
|
RDY, RUN, STA, ERR
|
| Operating voltage
|
5 V ±5% / 300 mA
|
| Operating temperature
|
0 °C - 55 °C
|
| Dimensions (L x W x H)
|
63 x 77 x 14 mm
|
| Weight approx.
|
150 g
|
| CE sign
|
Yes
|
|
|
|
|
|
|