Hilscher COM-COS
|
|
|
Hilscher COM-COS
|
Communication Module CANopen-Slave
COM-Modules are a simple and economical solution for the implementation of fieldbus interfaces. As a compact plug-in board it contains the entire CANopen including the potential-free driver interface.
The data exchange with the Host systems is carried out via an easy to handle interface, which has a dual-port memory that is the same on all models. Here, the process variables are carried in a process image, whilst commands are transferred over a mailbox. The module accepts the data and carries out the data exchange via the CANopen network, independently without any load on the Host system.
The configuration can be carried out with the aid of our SyCon® System Configurator, e.g. via the RS232C diagnostic interface.
|
|
|
|
|
|
|
| Facts at a glance: |
| Compact and economical CANopen interface |
| Direct connection to the CANopen network |
| Direct access to the process data in the dual-port memory |
| Identical 'easy-to-use' application interface to all COM modules |
| Interchangeable with COM modules of other fieldbuses |
|
|
|
| Product
|
COM-COS
|
|
|
|
| Description
|
Communication Module
|
| CANopen-Slave
|
|
|
|
| Card format
|
COM
|
|
|
|
| Bus interface
|
Dual-Port-Memory
|
|
|
|
| Dual-Port-Memory
|
8 KByte
|
| Interrupt
|
Yes
|
| Connector
|
Female post connector 40-pin
|
|
|
|
| CANopen interface
|
CiA DS-102
|
|
|
|
| Transmission rate
|
10 kBaud to 1 MBaud
|
| Controller
|
SJA 1000
|
| Interface
|
ISO 11898, optically isolated
|
| Connector
|
Male post connector 10-pin
|
|
|
|
| Diagnostic interface
|
RS232C, non-isolated
|
|
|
|
| Connector
|
Male post connector 10-pin
|
|
|
|
| Display
|
RDY, RUN, STA, ERR
|
| Operating voltage
|
5 V ±5% / 300 mA
|
| Operating temperature
|
0 °C - 55 °C
|
| Dimensions (L x W x H)
|
63 x 77 x 14 mm
|
| Weight approx.
|
40 g
|
| CE sign
|
Yes
|
|
|
|
|
|
|
Catalogue Entry
|
|
|