In automation, Ethernet is required to transmit large quantities of data with a high data rate over all levels of the communication pyramid at the low cost of office components. The truth is that different systems of data minimizing, minimal jitter and line topologies require additional hardware and only partly, or to a limited extent, permit the use of standard components. The often-demanded ten year supply guarantee means the use of special PC boards for automation.
With the cifX Hilscher provides a solution that supports all systems, that is reduced to the netX network controller and an SDRAM and thus offers the maximum of performance, functionality and flexibility at a fair price.
   
   
Facts at a glance:
One PC Card for all Real-time Ethernet Systems
One PC Card that runs Master and Slave Protocols
Data Exchange via Dual-Port Memory (DPM) or Direct Memory Access (DMA)
Unified User Interface for Various Protocols
PCI or PCI Express
Ten-year Commitment of Availability
SyCon.net Configuration Tool based on FDT/DTM Technology
   
Product CIFX 50-RE
   
EtherCAT Slave
   
Cyclic Data max. 400 Bytes
Acyclic Data SDO Master/Slave
SDO Slave/Slave
Functions 3 FMMUs and 4 SYNC-Manager
COE (CANopen over Ethernet)
Complex Slave
Emergency
   
EtherNet/IP Adapter
   
Cyclic Data max. 1008 Bytes
Unscheduled Data max. 1400 Bytes per Telegram
Functions Cyclic Connection
DHCP, BOOTP
one E/A Connection
max. 8 Connections
UCMM supported
Server Services Get_Attribute_All
Get_Attribute_Single
Set_Attribute_All
Set_Attribute_Single
   
PROFINET IO Device
   
Cyclic Data max. 2048 Bytes (IOCR)
Acyclic Data Read/Write Record, max 1024 Bytes/Telegram
Functions Context Management over CLRPC
DCP
Process- and Diagnostic Alarm
1 Submodul
Diagnostic, max 200 Bytes/Telegram
max. 244 modules
variance comparison of the configuration
VLAN- and Priority-Tagging
   
Modbus TCP/IP Server
   
Function code 1,2,3,4,5,6,15,16
Register (16-Bit) max. 120 or 125 Register per Telegram
Coil (1-Bit) max. 1968 or. 2000 Coils per Telegram
Message Modus In/Out-Data Image not used
Server
I/O-Modus Server max. 11520 Byte E/A Data
   
SERCOS III Slave
   
Realtime Data max. 2800 Bytes
Acyclic Data Service Channel Read/Write/Standard Kommands
Functions Max. 8 Subdevices
Phase Run Up
Ring and Line Topology
Synchronization
Version V1.1
   
EtherCAT Master
   
Cyclic Data max. 11520 Bytes
Acyclic Data CoE (CANopen over EtherCAT)Up-/Download
Functions Emergency
Get OD List
Topologie: Linie
   
EtherNet/IP Scanner/Master
   
Cyclic Data max. 11520 Bytes
Unscheduled Data max. 504 Bytes per Telegram
Functions Cyclic Connection
DHCP, BOOTP
max. 64 Connections
UCMM supported
Client Services Get_Attribute_Single/All
Set_Attribute_Single/All
   
PROFINET IO Controller
   
Cyclic Data max. 6144 Bytes
acyclic data Read/Write Record, max. 4096 Bytes/Request
Functions Alarm Handling
Context Managment over CLRPC
DCP
max. 32 Devices
minimum cycle time 1 ms
Pro Device one Puffer available for Diagnostic Data
   
PowerLink Controlled
Node/Slave
   
Cyclic Data max. 2980 Bytes
Acyclic Data SDO Up-/Download
Functions SDO über ASND und UDP
Poll Request/Response Response Time 1?s
Version V2
   
Technical Data
   
Interface PCI, 33 MHz DPM or DMA
Operating Voltage 3.3 V / max. 650 mA
Operating Temperature 0..55°C
Dimensions (L x W x H) 120 x 72 x 18 mm
Description Communication Interface PCI
   
   