LT-4V, LH-4V

LINE SPLITTERS

LT-4V, LH-4V


LINE SPLITTERS
LINE SPLITTERS
The asynchronous LT-4V and LH-V line dividers splitter a V.24-/M-1 modem connection into an RS485/V.24 interface and a V.24-/M-1 modem interface, the RS485/V.24 interface being galvanically insulated from the other interfaces. For example, this enables several RS485 networks at some distance from each other to be connected to a common station via the 4-wire M-1 modem interface, or enables several addressed input devices distributed in different buildings with RS485/V.24 interfaces to be connected to a common network. The data flow direction supports any master/slave networks and Multimaster networks (token passing). The distance between two LH-4V/LT-4Vís may be extended as far as 21 km, by means of the modem interface, the data connection being galvanically insulated by the optocoupler interfaces. After each line divider the data are transmitted in regenerated form. If one device fails, the line splitter is bridged with relay control, so that the modem connection is restored without data regeneration. This bypass function provides a high degree of data protection. The information contents and protocols are not influenced by the short device running times. The transient protection in the line dividers provides good protection against lightning and overvoltages, and the galvanic insulation provides protection where there are differences in potential. The LT-4V and LH-4V dividers meet the most stringent requirements regarding reliability, operation and performance, and their simple handling enable the devices to be installed without problem. The LT-4V is integrated in a small, compact tablemounted casing with its own power supply with an operating voltage of 230V AC. The LH-4V is the LT-4V for the 35 mm mounting rail and operates at a voltage of 24V DC. The signal status is displayed by means of LEDís (Power, TD, RD and DCD) on the front panel.
Example of application
Block diagram
   
   
Divides a connection into 2 interfaces
RS485/V.24 and V.24/M-1 modem interfaces
RS485/V.24 interface galvanically insulated
Conversion of the RS485 to V.24/M-1 Modem
RS485 direction detection: transmit/receive
0-100,000 bits/s, asynchronous
230V AC and 24V DC operating voltage
Bypass function
Simple installation
   
Technical data
   
Data transfer: Asynchronous; full-, half duplex or simplex
Interface 1: EIA RS232, V.24/V.28 or 10 mA sym
Tristate current loop, 4-wire transfer
Interface 2: EIA RS232, V.24/V.28 or EIA RS485
V.11 (2-wire);
Galvanically insulated
Schnittstelle X3: EIA RS232, V.24/V.28 or 10 mA sym
Tristate current loop, 4-wire transfer
Transfer speed: 0-100,000 bits/s, code-transparent
Connections: LT-4V: All connections as 5-pin plug-in screw terminal
LH-4V: Via DIN 41612 connector or via 35 mm support rail assembly base with screw terminals.
LED displays: Network, TD, RD and DCD (interface 1)
Insulation: Galvanic insulation of data transfer by optocouplers
network insulation by transformer (LT-4V with 230V AC only)
Interface 2 Insulated from interface 1 and 3 by optocouplers and protective ground.
The protective conductor connection is used only for discharging interference voltage
Insulation voltage: 420 Vrms
Supply voltage: LT-4V: 230V AC + 15%, 50/60 Hz
LH-4V: 24V DC + 10%
Network cable: Detachable, 1.8m (LT-4V only)
Current consumption: LT-4V: 25 mA maximum
LH-4V: 200 mA maximum
Temperature range: 5-50°C ambient temperature
Humidity range: 0-95% relative humidity
Dimensions, in mm: LH-4V: 129 x 47 x 134 (WxHxD) assembly base excluded
Assembly base 75 x 100 x 25 (WxHxD)
Casing material: Plastic ABS, black
aluminium back
Weight: LT-4V: 0.5 kg
LH-4V: 0,25kg, assembly base add 0.1 kg
Assembly: LT-4V: Rubber pads or Velcro tape
LT-4V: by assembly base on 35 mm DIN mounting rail (EN 50022)
Conformity: CE
   
Range of the M-1 modem interface
Range of the M-1 modem interface
Range of the RS485 interface
Maximum transfer distance 1200m at 0-100,000 bits/s
 
Other model versions
LT-1V: As LT-4V, all interfaces as V.24/M-1 modem
LH-1V: LT-1V for 35 mm DIN mounting rail