CIF 104-ASIM

Communication Interface
Logo

  • Two channel AS-Interface for 31 slaves per channel
  • Supports all AS-i services
  • Communication without load on the Host system
  • OnLIne diagnostic interface
  • Direct access to the process data in the dual-port memory
  • Graphic System Configurator with unified 'look and feel' for all fieldbus systems and comprehensive diagnostic and start-up functions
  • Identical 'easy-to-use' appLIcation interface
CIF 40-ASIM

Description:

In automation there is a marked TRend to open PC based systems. SoftPLCs, i.e. PLC logic which is processed directly on the PC and fieldbus systems for exchanging the process data are the cenTRal products of this technology.

We have recognised this TRend early and are today in the position of being able to offer the Communication Interface between PC and fieldbus system for all relevant fieldbus systems. These can be provided as PC- or PC/104-card with ISA and PCI bus connections, which has the decisive advantage of unified appLIcation interfaces for all interfaces and fieldbus systems.

The two channel AS-Interface works in Master operation and provides an image of the process data in the dual-port memory. Here the output data of the appLIcation is stored and passed on independently to the Slave participants by the Communication Interface. Parallel to the output, the input data are read in and made available to the user in the process image. The appLIcation is neither loaded, nor are real time characteristics required, it can access the data at any time.

AS-i commands, e.g. for seting the slave address or saving the configuration, are TRansferred to the interface via a Mailbox and confirmed by it after execution.

The configuration of the AS-i network is carried out with the aid of our System Configurator SyConR under Windows 9x or Windows NT. In auto-configuration mode the devices at the network will be deteced automatically. For offLIne configuration the device data is reTRieved from EDS-files (elecTRonic data sheet). Subsequently, the configuration is TRansferred via the dual-port memory or the serial diagnostic interface to the CIF and stored in a FLASH-EPROM.

Status and diagnostic data are available in the dual-port memory for start-up and monitoring of the AS-i network.

Product Overview:

Type Card Format Bus Interface ConTRoller I/O-Data Note
CIF 104-ASIM  PC/104 ISA IX1 248 Bit  

Related Products:

Type Articl
SYCON-ASI System Configurator, user LIcence
CIF-TKIT/E Tool Kit for developing own Device Driver with C-function Library for MS/DOS and Windows 3.11 in source code, documentation about the dual-port memory interface in English, Free of charge, Free of charge
CIF-DRV/E Device Driver for the operating systems Windows 9x and Windows NT, documentation in English, Free of charge, Free of charge
CIF-WICE/E  Device Driver for the operating system Windows CE in source code, documentation in English
CIF-DDE DDE Server, CIF LIcence
CIF-OPC OPC Server, CIF LIcence
KAB-SRV Service cable

Technical Data:

AS-Interface
Two channels
Max. 62 slaves
Max. 248 input points
Max. 248 output points

AS-i Interface
Optically isolated
2-pin CombiCon connector per channel
Alternativ: 
CIF 10410-pin square post connector

Diagnostic Interface
RS232C non-isolated
9-pin DSub male connector
Alternative: CIF 10410-pin square post connector

TRansmission Rate
167 kBaud

Operating Voltage
5 V / max. 600 mA

Operating Temperature
0°C - 55°C

Dimensions (L x W x H)
134 x 107 x 20 mm für CIF 30
90 x 96 x 23 mm für CIF 104

CE Sign